EGCON-AVR

kimswed 2008.04.16 21:09 조회 수 : 2273 추천:306

extra_vars1 |||||||||||||||||||||||||||||| 
extra_vars2 ||||||#5000AF|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||| 




CONTROL PARTS     |     AVR  (Automatic Voltage Regulator)


MODEL : 635
FUNCTION
1. Single Phase half-wave rectification
2. A/S support
3. Selection switch for generator capacity is included
4. Selection switch 50Hz~60Hz frequency is included
5. Low Frequency Protect Circuit is included
6. Anti Over Voltage Circuit is included
7. Noise filter (Input power type) is included

SPEC.
1. Output : 63Vdc, 5A
2. Input power : Single Ph 220Vac(190~277), 50/60Hz
3. Sensing Input :Single Phase,190~520Vac, 50/60Hz
4. Size(mm) : W95*H160 *D37
5. distance[attach](mm) : W60*H150, 5¢ x4
6. Weight : 530g


MODEL : 631
FUNCTION
1. Single Phase half-wave rectification
2. A/S support
3. Selection switch for generator capacity is included
4. Selection switch 50Hz~60Hz frequency is included
5. Low Frequency Protect Circuit is included
6. Anti Over Voltage Circuit is included
7. Noise filter (Input power type) is included

SPEC.
1. Output : 63Vdc, 10A
2. Input power : Single Ph 220Vac(190~277), 50/60Hz
3. Sensing Input :Single Phase,190~520Vac, 50/60Hz
4. Size(mm) : W95*H160 *D37
5. distance[attach](mm) : W60*H150, 5¢ x4
6. Weight : 530g


MODEL : 63P
FUNCTION
1. Single Phase half wave rectification
2. Anti-humid and vibration by molding treatment
3. Select S/W for 50/60Hz is included
4. Selection switch for generator capacity is included
5. Low Frequency Protect Circuit is included
6. Anti Over Voltage Circuit is included
7. Noise filter (Input power type) is included

SPEC.
1. Output: 63Vdc, 5A
2. Input Power : Single Ph. 220Vac, 50/60Hz
3. Sensing Input : Single Ph, 190~520Vac, 50/60Hz
4. Size (mm) : W95*H160 *D37
5. distance[attach](mm) : W60*H150, 5¢ x4
6. Weight : 360g


MODEL : FC1
FUNCTION
1. Single Phase full wave rectification
2. Parallel Running Function
3. Select S/W for 50/60Hz is included
4. Select S/W for Generator capacity is included
5. Low Frequency Protect Circuit is included
6. Detect Over voltage output
7. Volt control is available extra controller
8. Extra Huse for semicon protect is included
9. Possible Input power from PMG or auxiliary winding

SPEC.
1. Output : 125Vdc, 6A
2. Input PW : Single Ph 220Vac(190~277),50~125Hz
3.Detached input :Single Ph,190-520Vac, 50/60Hz
4. Size (mm) : W140*H200 *D40
5. distance[attach](mm) : W90*H190, 5¢ x4
6. Weight : 1.35Kg


MODEL : FC2
FUNCTION
1. Single Phase full wave rectification
2. Select S/W for 50/60Hz is included
3. Select S/W for Generator capacity is included
4. Low Frequency Protect Circuit is included
5. Detect Over voltage output
6. Anti-humid and vibration by molding treatment
7. Possible Input power from PMG or auxiliary winding

SPEC.
1. Output : 125Vdc, 6A(750W)
2. Input PW : Single Ph 220Vac(190~277),50~125Hz
3. Sensing Input : Single ph,190-520Vac, 50/60Hz
4. Size (mm) : W140*H200 *D40
5. distance[attach](mm) : W90*H190, 5¢ x4
6. Weight : 690g


MODEL : CT1
FUNCTION
1. Single Ph half wave rectification for Catafila product
2. Anti Humid & vibration treatment by silicon coating
3. Detact 3 Pahse 220V
4. Parallel running circuit is included
5. Detact Over volt input signal
6. Low Frequency Protect Circuit is included

SPEC.
1. Input Power/Sensing : 3Phase 220Vac
2. Output : 63Vdc, 10A
3. Voltage Regulation : ±1%
4. Size(mm) : W130*H160 *D53
5. distance[attach](mm) : W60*H150, 5¢ x4
6. Weight : 700g

발전기의 전기적 耐量

1발전기 권선의 단시간 과전류 내량

고정자 및 회전자권선의 단시간운전에 대해서 허용치가 규정되어 있다. 이는 주로 열적인 제한이며 시간과 용량관계에서 규정된다. 발전기의 고전류 운전을 하는 경우 회전자의 과전류 운전의 영향은 동 BAR 의 최고온도가 130℃ 이하에서는 문제가 없으나 150℃-160℃로 되는 온도변화의 반복이 있는 경우 권선의 수명 단축이 되나, 부하변동에 대한 내력저하 등의 영향은 적다. 따라서 과부하 운전은 년간 2회 까지 가능하다.

2. 역상내량

발전기를 불평형 부하 운전한 경우에 흐르는 역상전류에 의한 회전자 표면의 과열은 설계 및 운전상의 중요한 과제이다.
TBN발전기에 대하여서도 계통 운용상의 필요성으로 부터 역상내량을 구정하고 있다.
역상내량을 회전자 표면의 열방산 정도에 따라 과도적인 불평형 내량과 연속적인 불평형 내량으로 나눌 취급되며 각각 단시간 역상내량, 역속 역상내력이라 한다.
역상전류는 상기한 바와 같이 발전기를 불평형 부하 또는 단상부하로 운전하 게되면 고정자 Coil에 역상전류가 흘러 회전자계와 동일한 속도로 반대방향으로 회전하는 회전자계가 회전자와 쇄교함으로서 2배의 주파의 와전류가 회전자 표면, 회전자 Wedge에 흘러 회전자가 과열된다.
특이 와전류가 집중되는 부분에서는 국부적 과열로 소손을 일으키는 수도 있다.
불평형 부하의 허용한계는 기기의 재료, 구조에 크게 좌우되어 한가지로 규정할 수 없으나 ANSI C50-13에서 제한되고 있다.

한편 역상전류에 의한 과열현성을 완화하기 위해 회전자 표면의 와전류 회로에 여러 가지 대책이 취해지고 있으며 통상 대용량 TBN발전기에서는 다음과 같이 행해지고 있다.

가. 비자성 재료로 된 은도금을 한 단락 BAR 및 Ring 을 철심단 Wedge 과 End Ring밑에 삽입한다.
나. 회전자 권선 Slot부에는 비자성 Wdege를 채용하여 와전류 손실를 경감 하고 있다.
다. 특히 전류가 집중하기 쉬은 철심단부에는 열적으로 강한 Stainless계 비자성 Wdege를 채용하고 있다.
라. End Ring과 회전자 축의 열처릴 접축부에 Metallizing를 행하여 분류회로가 되는 End Ring과의 접촉 저 항을 낮추고 있다.
마. 와전류의 회로가 되는 Wedge와 회전자 Teeth 부를 잘 손질하여 접촉저항을 낮춘다.

3. 발전기의 과여자 특성

발전기는 그 단자전압이 ±5%이내의 변동볌위에서 정격출력을 발생할 수 있어야 한다. 이 변동범위를 초과한 운전에 있어서 95%이하의 전압에서는 전기자 전류가 정격치가 되도록 KVA출력도 저감되어야 하며 진상영역에서는 고정자철심 단부의 과열방지를 고려하여 엄격히 제한하고 있다.
한편 105% 이상의 과전압 운전에 있어서도 자기회로의 과포화를 피하기 위하여 엄격한 제한치가 설정되어있다.
과여자 운전의경우, 발전기 내의 자속량이 증가하고 그 결과 자기회로가 과포화 상태로 되어 특히 고정자 철심내에서는 철손이 증가하여 과열의 원인이 된다. 대단히 심하게 과여자 운전한 경우 단시간에 사고로 발전할 가능성이 있고 과포화의 정도가 경감됨에 따라서 시간은 길어지는 경향에 있다. 따라서 과여자의 정도와 허용운전시간의 관계에서 운전을 제한 할 필요가 있다.
최근에는 이 과여자를 V/Hz 로 하여 평가하고 있다. 예를 들면 1.1PU에서 100분, 1.2PU에서 약 30분 정도 운전이 가능하나, 발전기에 따라 다르다.

* kimswed님에 의해서 게시물 이동되었습니다 (2010-07-16 13:57)